EN 14303: Thermal insulation products for building equipment and industrial installations - Factory made mineral wool (MW) products - Specification
Standard: EN 14303 - Thermal insulation products for building equipment and industrial installations - Factory made mineral wool (MW) products - Specification.
Certification: CE Marking
Factory made mineral wool (MW) products for building equipment and industrial installation should meet the requirements as described in the standard EN 14303, which is a harmonized standard under the Construction Products Regulation (EU) 305/2011.
Scope: This European Standard specifies the requirements for factory made mineral wool products, which are used for the thermal insulation of building equipment and industrial installations with an operating temperature range of approximately 0 °C to + 800 °C.
Below an operating temperature of ambient, special means against water vapour diffusion and water accumulation by air flow might be required. Below an operating temperature of - 50 °C, special tests regarding the suitability of the products in the intended application are advised (e.g. liquefaction of oxygen). Manufacturer's advice should be heeded in all cases.
The products are manufactured with or without facings or coatings, in the form of rolls, boards, slabs, mats, felts, quilts, wired mats, lamella mats, bevelled lags and pipe sections.
Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered.
This European Standard does not specify the required level of a given property that should be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application can be found in regulations and invitations to tender.
Products with a declared thermal conductivity greater than 0,065 W/(m·K) at 10 °C are not covered by this standard.
This European Standard does not cover products for in situ insulation (blowing or pouring) or products for the insulation of the building structure.
This European Standard does not cover the following acoustical aspects: direct airborne sound insulation and impact noise transmission index.
Related Standards:
- EN 13172: Thermal insulation products — Evaluation of conformity
- EN 13501-1: Fire classification of construction products and building elements — Part 1: Classification using data from reaction to fire tests.
- EN 13823: Reaction to fire tests for building products — Building products excluding floorings exposed to the thermal attack by a single burning item
- EN 12667: Thermal performance of building materials and products — Determination of thermal resistance by means of guarded hot plate and heat flow meter methods — Products of high and medium thermal resistance.
- EN 12939, Thermal performance of building materials and products — Determination of thermal resistance by means of guarded hot plate and heat flow meter methods — Thick products of high and medium thermal resistance
You may be interested in...
Intertek provides Insulation Testing services for performance and environmental determining the level of fire resistance and energy efficiency of your materials
Knowledge Center
Building Health & Wellness: An Overview of Services
Acoustical Testing & Consulting Resources
Remote Pre Inspections for NFPA 80 / 101
Protek - Safety. Everywhere. Every Day
Fire Doors 101: Your Guide to Testing and Certification - Webinar Recording
Tornado Testing & Certification Requirements - Webinar Recording
Plumbing Products Testing & Certification - Webinar Recording
The Evolving Code Evaluation Process White Paper
Proposition 65 & the Furniture Industry Webinar Recording
Why Planning for FCC Certification is Key to Success in the Door Hardware Industry White Paper

Upcoming Tradeshows & Events
Resources
- Search and Buy Building & Construction Standards
- SpecDirect
- Building Products Directory
- Project Connect (formerly myATI) – B&C Products
- Construction Hive – B&C Projects (PSIQest)
- My TestCentral